How to Test and Tag a 3 Phase Appliance
Leakage Test
We'll need to use our Portable Appliance Tester and Leakage Current Meter to conduct the test. A Leakage test is required if the appliance has electronic/magnetic switching (contactor blocks).
For a PASS, you require:
- Leakage test has to be less than 5mA
It's important to wait a few seconds for the number of your reading to level out. When disconnecting the system, ensure you do it in reverse by turning the meter off first, followed then by the appliance and mains power.
If you're needing help choosing the right 3 Phase testing equipment, please contact us on 1300 848 302.